Tech returned and replaced failed start kit. Recovered 1 lb 8 oz of remaining R22 in system. Flowed nitrogen while brazing in new indoor coil and filter drier. Threaded in new indoor TXV and tightened with two adjustable wrenches. Pressure tested to 200 psi nitrogen. System passed standing pressure test and soap bubble test. Evacuated system to 200 microns. System passed 20 minute standing vacuum test. Recharged with 5 lbs 10 oz of R22 plus 4 oz for 30 foot lineset. Tested system without challenges. Tech collected for repairs. Customer placed both split systems on regular Comfort Plus plan. First visit in 6 months.