Tech preformed CMA INSPECTION on 9 RTUs, 5 Mini Split Systems, and 2 Gas Hanging Heaters. Upon inspection of RTU #1 Tech found that Heat Strips are non functional due to a previous short that caused a wires to burn. Tech unsure cause of issue. Tech did find that a fuse had been pulled from fuse block. Unsure if these was done to prevent any further damage. Recommend replacing heat strips and fuses to further diagnose issue. Being Heat Strips are 460v Office will have to call with further pricing. Tech removed low voltage wire that controls Auxiliary Heat from board to prevent any further damage. Refrigerant issues still exist for RTU #6, #7, and #8. Leak searches were preformed in Sept. 2023 and Office was supposed to send quote. Mini Split System #3 also still has leak that was diagnosed in Sept. 2023. All other Systems are operating at this time. Tech has attached SYSTEM PERFORMANCE REPORTS to invoice along with pictures.