Ansul Fire Suppression System/Fire Extinguishers/Exit&Emergency Lights - Code Deficiencies (Replacement Needed) During the most recent Fire Protection Inspection, our technicians identified several deficiencies in the Ansul fire suppression system, fire extinguishers, and exit/emergency lighting. These issues must be addressed to ensure compliance with ANSI, NFPA, and UL 300 standards, as well as manufacturer specifications. Identified Deficiencies: Ansul Manual Pull Station: The pull station is severely corroded, stuck in place, and failed to operate during testing. Replacement is required. Ansul Cartridge: The existing Ansul 101-30 cartridge on the 9-gallon system is incorrect for the system size. It must be replaced with an Ansul double tank cartridge per manufacturer requirements. Ansul Nozzle and Swivel Replacement: One Ansul nozzle and two nozzle swivels need replacement to provide proper coverage for the appliance lineup. Exit/Emergency Lighting: The green/white exit light loca