Corrigo Portable Extinguishers, Emergency / Exit Lights, and Kitchen Suppression Inspection 3: FP Annual (3) 6: FP Annual (6) Ansul R102 6 gal: FP Semi Annual Ansul R102 3 gal: FP Semi Annual Deficiency for 6: Ansul 6 Gallon ( Manifolded ) system is 2 years past due for required 12 year maintenance ( 2010 ) System needs In-line burst disk installed to meet Ansul requirements for a manifolded system. Old 2 piece nozzles need to be replaced on Fryer hood. The system is Red-Tagged 1- double tank cartridge 1- in-line Burst Disk 2- Ansulex 2- Tested Tank 2- O-Ring 2- Burst disk 1- regulator test 2- hose assembly 3- 230 nozzle 2- 2120 nozzle 2- 1N nozzle