Job Checkin

Kitchen Suppression Repair Ansul R102 6 gal: 2 - 2012 6 gal ansul system due for hydro test system is manifolded. Will need in line burst disc. For both systems. - repair Ansul R102 6 gal: Both systems need burst disc at tie in - repair Ansul R102 6 gal: Hose on second system is rubber and sits outside of the automan so it must be a replaced with braided hose - repair Deficiency for Ansul R102 6 gal: 2 - 2012 6 gal ansul system due for hydro test system is manifolded. Will need in line burst disc. For both systems. Deficiency for Ansul R102 6 gal: Hose on second system is rubber and not braided Deficiency for Ansul R102 6 gal: Both systems need burst disc at tie in 12yr Hydrostatic Test Due: (1) Ansul 6-Gallon System (2012 Manufacture Date) (1) Ansul 6-Gallon System (2012 Manufacture Date) During your most recent Fire Protection Inspection, our technicians noted that one or more of your Fire Suppression Tanks are due for a hydrostatic test per: NFPA 17A: 7.5.1 The following parts of