Found loose spade connection had come off heat strip and caused a short causing the primary breaker to trip Also found the secondary breaker wire to be very undersized along with the breaker in the panel Fixed the loose connection Turned off secondary breaker and informed the homeowner of that issue Adjusted outdoor compressor lockout temperature Left unit on in heating