Performed evaluation Drain line has clog - secondary through side of home is releasing water - water is not built inside of drain pan due to drain line configuration Reccomended drain clear Washed condensor and tightened connections Capacitor was very low on tolerance - replaced capacitor - unit failed to operate beforehand Homeowner joined home and budget plan Filter will be replaced by homeowner since it does not have alot of build up System left on cool at exit
Arrived for super tune up Delta 19/23 refrigerant is good All heating and cooling components are in tolerance Replaced filters Reccomended IAQ200 replaced systems for current UV Lifetime warranty on module/3 yr warranty on bulbs - 4-5 yr replacement of bulbs New UV system clears both surface and air quality Reccomended whole home surge protection System left on cool at exit
Customer flapper had tiny leak on it adjusted flapper in tank and tested after adjusting toilet is brand new came with home. Toilet flapper no longer leaking in tank.
Replaced shut off valve for toilet in master bathroom. Tested after repair was made everything working properly. Customer declined the membership at this time said house is brand new.
On arrival downstairs system was off. After diagnosing I found the downstairs system to have a grounded compressor. The upstairs system was rejecting very hot air so I amp clamped the compressor and found it pulling 20 amps out of an rla of 13.5.