9/12/25 Evaluated system. Customer stated there was water leaking around the indoor unit. He removed the doors and noticed very dirty air filters and turned the unit off. I noticed the indoor coil and blower are in need of deep cleaning. I turned the unit on and the blower started up normally. I measured the refrigerant levels and they were within specs. My opinion is that the coil iced up due to low airflow created by the dirty filters, coil, and blower. My recommendation is to schedule a thorough system cleaning. Mr Plowman is going to observe the unit for icing up periodically and call us if he notices ice buildup over the weekend. If it works without icing we need to schedule a thorough cleaning the first part of the upcoming week. If icing is observed we will need to get it done sooner. Mr Plowman is also concerned about low airflow out of the vents and not keeping up in the summer. I recommend a comfort advisor to do a load calculation and duct inspection to solve these issues.