On arrival system running and cooling producing 20 degrees delta. Indoor unit in good condition and drain line flowed when flushed. Outdoor unit passed all electrical testing but compressor saver kit is non functional and contactor is buzzing loudly. Recommended replacing both but customer is planning on moving in next year. System cooling as I left.