1412 Greenwood Road
Weatherford, TX 76008
817-596-4808

Our Top Cities


Job Locations
for cresson, tx


Map of Cresson TX
Brady F.

Brady F.


Job Checkin

Main house inspection found electrical service mast and meter not secured properly and pulling away from house. Main panel located in laundry room with water heater directly in front of panel. Very loose main lug terminals found and tightened. Secondary service has direct burial service conductors laying on ground crossing walkway and driveway. Aluminum conductors used without anti-ox paste. No conduit to auxiliary panel. Secondary panel does not have panel grounded properly. Found burned neutral conductors in attic in splice. Installed 3 jct box's in attic for splices.