Performed cooling tune up Washed condensor and tightened connections Filter not replaced - not provided - reccomended to replace soon System delta 17 Reccomended indoor/outdoor PSC motor - loose rods/bearings Reccomended primary electrical control unit - gashed terminals/burn Reccomended Soft start kit - system high LRA Reccomended IAQ200 UV - Supply has Mass biological growth Reccomended home and budget plan Scheduled Service to IAQ - Zak Thursday 07/31/25 Morning Preferably Future reccomendation created at homeowner request for potential issue System has 11 SH 5SC Reccomended TXV Reccomended Filter dryer Reccomended Refrigerant - system is low on refrigerant but is performing at minimum standard Scheduled IAQ expert to evaluate system/air quality and provide guidance for rejuvenation Reccomended comfort advisor System left on cool at exit