Tech recovered refrigerant charge, removing 21lbs of R-410. Cut disconnected compressor and removed. Installed new compressor, obtained and replaced filter drier. Pressure tested, evacuated and recharged with 21 lbs of R-410. Operating specs were 140/390 SH of 13 SC of 9. System is back up and running. Installers are returning to make changes to the ductwork.