On this job I looked at duct work and system for both up and down stairs. Heating / cooling Concerns 1. Dirty supply vents / blower motor 2. System 1 upstairs unit needs real seal. To much cracks and air leakage. 3. System 2 low super heat 22° should be 15° 4. System 1 weak cap high inrush amps 5. System 2 high inrush amps and worn out contactor pads. 6. No water safties on either system Recommendations 1. Leak search system. Fix and add freon. 2. Easy start for both systems to tackle high inrush. 3. Replace capacitor 4. Level 2 duct cleaning for both systems. 5. Reseal system air leakage. 6. Maintainace plan. For routine cleaning and tolerance check. 7 water safties x2 8 ground both condensors propley.********* This is code**************