Upon arrival for evaluation I found outdoor condenser to not be coming on, I checked voltage and had high voltage but not low voltage. I then checked indoor and it had a safeT switch installed but there was no clog. I checked 24 voltage path and everything looked correct I then bypassed safeT switch to check function and system started working. I then tested safeT switch and found it to still be operating as it should I then checked drain line and found some buildup inside line that was causing safeT switch to trigger and cut 24v circuit I cleaned out gunk and rewired safeT switch and system stayed operational. Checked drain line with water and there was no clog just that little bit of gunk causing the sensor to go off. System started cooling and operating as it should System left on cool upon departure.