For this job I did an evaluation. Homeowner was concerned about some of the noises made when the system starts/stops operating. Did a thorough inspection and found nothing out of the ordinary. Changed filter. Recommend adding April Air to improve air filtration and prevent bypass dust. UV bulb has gone out. Went over benefits of replacing bulb vs. upgrading UV system. Compressor rated for 118 start-up and currently starting on 147 amps. Recommend soft start to extend compressor life and reduce load on start up. Homeowner declined work for today. Updating membership plan to H&B System cooling when I left.