51 Koweba Lane
Indianapolis, IN 46201
(855) 932-6437

Our Top Cities


Job Locations
for millersburg, oh


Map of Millersburg OH
Travis S.

Travis S.


Job Checkin

FP Semi-Annual FP Annual FP Annual Deficiency: Fryer hoods need the nozzles dropped. Per manufacturer specifications the nozzles are too high for proper coverage. 7 total nozzles need dropped. 12-14in black pipe nipples are needed Grill hoods also need Repipe. Griddle coverage is not up to manufacture specifications. 1 H nozzle needed to replace non UL300 nozzle Kitchen Suppression, Portable Extinguishers, and Emergency / Exit Lights Inspection