7/30/21  confirmed with karen for Thursday  8/5/21  sM Karen will be in @ 3:00   PM  Friday. 2/1 NA at 11:30 AM. Google says they're open, emailed Karen again. km 12/21 NA no vm option, emailed Karen. km Portable Extinguishers and Kitchen Suppression Inspection Annual Extinguisher Inspection ( 5 FEs ) Semiannual Kitchen Suppression System Inspection ( 1 Ansul 3G, 1 Pyrochem 4.6G ) Deficiency: Ansul system has a red button automan. Inoperable Deficiency: Discharge warning device has dead battery. Deficiency: Three 2012 5# ABC extinguishers due for 6yr. maintenance. Replacement with hydro’d units suggested. Deficiency: Discharge warning device does not operate during system actuation on main hood system. Deficiency: Number of Systems failed : 1