9/10/21  confirmed with Nick for Monday   9/13/21  SM 8/12 Requested by and confirmed with Dan, owner.   His cook will come in early to let you in. km Portable Extinguishers and Kitchen Suppression Inspection Annual Fire Extinguisher Inspection (2)ABC's (1)BC (1)K-Class Semiannual Kitchen Suppression System Inspection ( 1 RG725 ) Deficiency: 1 5lb abc Ansul was condemned needs to be replaced. Need additional 2 units to bring restaurant up to NFPA 10 code. Deficiency: Number of Extinguishers Left at Job: 1 Deficiency: Number of Systems failed : 1 Deficiency for Range Guard RG 6G+2.5G Wall Across from Main Hood: System does not have a discharge warning device. Deficiency for Range Guard RG 6G+2.5G Wall Across from Main Hood: Electric non fuel source on convection oven and 110v outlets under main hood do not de energize upon fire system actuation.