11/20/23 Sent email regarding inspection DH / Sprinkler Inspection Annual Fire Sprinkler Inspection (1 Wet System) Tech will need to bring (2) water gauges on 2023 inspection 5-Year Internal Due: 2023 FDC Hydro Due: 2023 Deficiency for Wet Training room closet: Outdated water gauges x2 Deficiency: Return trip required to pipe out ITV. Lift required Hilo to short 1- 1” ball valve 2- 1” galv wall plates 2- 1” 90 1- 1”x 3/4”galv 45 2- 3/8” drop in anchors 2- 1” cls ptrn ring 1-3/8” TBC 3/8” ATR 1- 1” loop ring 1x 3/4” 155 brass upright for head box 1- ITV sign w/chain 42’-0” 1” Deficiency: Inspectors test valve on side of building up front is intact and just needs a sprinkler head to reduce it 1- 1/2” brass, 155° sprinkler head half-inch orifice. Deficiency: Sprinkler system fire department connection check valve is due for internal inspection of valve Deficiency: Sprinkler system is due for five year internal pipe investigation for obstructions. 1- 4” victaulic coupling Deficiency: