2710 Northridge Dr. Suite #F
Grand Rapids, MI 49544
1-800-968-2871

Our Top Cities


Job Locations
for pontiac, mi


Map of Pontiac MI
Terrence  J.

Terrence J.


Job Checkin

11/20/23 ,Confirmed with Bob Davis for 12/1/23. Please call Bob when you arrive 248-762-9133 10/17/23 Left VM regarding Inspection DH Sprinkler and Stand Pipe Inspection Annual Fire Sprinkler System Inspection (3 wet, 1 dry) Annual Standpipe Inspection (2) Deficiency: Gauges are outdated 6 wet 1 dry Deficiency: System check, bypass check, discharge check and fdc check due for 5yr internal Gasket material 4- 6” red rubber gaskets 2- 4” grooved couplings Deficiency: System pipe due for 5yr internal 6- 4” grooved couplings 3- 3" grooved couplings Inoperable Deficiency: Fdc check leaks by and fdc pipe needs to be reworked outside. Addition built around fdc making it inaccessible 21’ 4” sch10 black 2- 4” grooved couplings 1- 4" viking check Deficiency: Fdc pipe due for hydro x2 Deficiency: Missing control valve, itv and main drain signs 17- control valve 5- main drain 1- itv 3rd floor by roof access 23- sign chain Deficiency: Missing spare heads and head wrenches fire pump room 2-