2/21/24 Sent email regarding inspection DH Sprinkler Inspection Annual Fire Sprinkler Inspection (1 Wet System) Deficiency: Missing, concealed head wrench, in head box for a tyco 3531 Deficiency: Fire sprinkler system is due for gauge change. 1- sprinkler gauge Deficiency: The sprinkler system is due for five year internal inspection, fire department, connection, check valve. 2- victaulic couplings Deficiency: Sprinkler system is due for five year internal obstruction investigation of piping. 2- 4” victaulic couplings Deficiency: One control valve sign for lower control valves needed. 1- control valve sign Deficiency: Fire sprinkler system is due for five-year Hydro test. Deficiency: Missing, concealed head wrench, in head box for a tyco 3531