8/22/25 Evaluated dryer circuit. Initial readings at the receptacle were phase 1 to phase 2 = 244 volts. Phase 1 and phase 2 to ground 80 to 83 volts. Wire is spliced at non-accessible junction box beside sink that was added during a remodel. Recommend replacing with dedicated circuit from panel to dryer in flexible conduit through attic due to living in the country where mice are present. Total for circuit would be $1,724 - club savings $344.80 = $1,379.20. Circuit replacement needs to be scheduled for Tuesday August 26.