1412 Greenwood Road
Weatherford, TX 76008
817-596-4808

Our Top Cities


Local Reviews
for krum, tx

Rated 5.0 out of 5 stars based on 2 customer reviews

Great service!

Steven was very knowledgeable! Was a great experience! Highly recommend!

  • Overall Experience
  • Quality
  • Price
  • Convenience

5 Stars

Kind knowledgeable efficient!

  • Overall Experience
  • Quality
  • Price
  • Convenience

Job Locations
for krum, tx

Mike R.

Mike R. Job Checkin

System had low voltage rub out blown fuse. I fixed and put a new fuse in it.


Shantel Z.

Shantel Z. Job Checkin


jonathan.brockway@acgenius.com

jonathan.brockway@acgenius.com Job Checkin

I changed the filter blower is dirty systems needs a level 2 duct cleaning heat strips in tolerance capacitor outside was out of tolerance I changed it out


adam.brockelman@acgenius.com

adam.brockelman@acgenius.com Job Checkin

Crawled inside crawl space of home and repaired 2 separations on main sewer line. 1 break under washing machine and 1 break towards back of home. tested after repairs were Made everything working properly.


Lisa M.

Lisa M. Job Checkin


Jerred G.

Jerred G. Job Checkin

Today I performed a heating Tuna on a 10 year old heat pump unit I looked through everything indoor as well as outdoor running in heat mode pulled the blower and inspected it as well as the heat strips that are within range as far as amp draw got pictures of the return and supply plenum as well as the evaporator coil which is severely restricted due to animal hair dust and organic growth I flushed the drain line with white vinegar but was unable to replace the dirty filter as the homeowner did not have an extra one on hand both capacitors indoor and outdoor are within range but slipping photos to show actual reading and percentages the compressor is drawing an amperage that exceeds manufacturers limitations upon startup I washed the condensing coils thoroughly and provided before and after photos I presented the homeowner with my findings and recommendations discussing the home and budget protection plan as well as financing unfortunately we were unable to take care of anything today a


Mike R.

Mike R. Job Checkin

On this job I washed the condensor and changed the filter. The subcool is 8 and td is 20. The system could use a soft start and some uv for the air handler. System is now back online and ready for cooling.


colby.finch@acgenius.com

colby.finch@acgenius.com Job Checkin

On arrival system running and cooling producing an 18 degree delta. Indoor unit was clean and in good condition. Filter did not fit well, recommended April aire filter upgrade to remedy this. Outdoor unit passed all electrical testing. When I left system was running and cooling.


Daniel S.

Daniel S. Job Checkin

Arrived for rec work Installed new motor and system running before I left


Daniel S.

Daniel S. Job Checkin

Arrived at eval Customer stated the system iced up Ran test and found out the system is extremely dirty and the blower was out Relayed information to customer about this Ordered warranty motor, customer didn’t want to do temp Holding for parts


garrett.young@acgenius.com

garrett.young@acgenius.com Job Checkin

For this evaluation, customer stated unit shut off randomly and then came back on late at night on its own. When we went to the attic there was water in the primary drain line and a lot in the secondary drain line. The vent to the primary was capped not allowing water to drain properly. Once that was cut and water poured down the line it started to drain like normal. We checked under the sink at the p-trap and there was a clog in there. Once cleared all the water came pouring out.


Lisa M.

Lisa M. Job Checkin


Zak L.

Zak L. Job Checkin

Arrived for service call Water in the secondary drain pan because vents were installed incorrectly Sealed vents to prevent air flow from preventing water drainage Refrigerant capacitors age Motors are fine System cooling at exit


Diane P.

Diane P. Job Checkin

Install 42k Intertherm upflow electric with standard filtration, code kit


Daniel S.

Daniel S. Job Checkin

Arrived for Eval Ran test and figured the system was low on refrigerant, the suction line was in insulated. Relayed information to customer and we talked about doing a new system Customer was pre approved for 25,000 Comfort advisor visit for 05/29/24 6-8