FP Semi-Annual FP Annual FP Annual Inoperable Deficiency: Back door exit combo light is damaged and inoperable. Needs replaced with an LPI-ELED4 light. Inoperable Deficiency: Hood 1 detection line failed. 4 total Ansul link detectors, not welded in. 8-10ft of conduit. Grease in conduit is preventing line from working. Non UL 300 nozzles in use. Red tag issued for hood 1 1-1W nozzle 3-1N nozzles Hood 2 in use of Non UL300 nozzles as well. Hood 2 also needs stainless steel scissor link holders to replace old style holders. Re pipe of nozzles over clam shell appliance needed. 1-1W nozzle 3-1N nozzles Kitchen Suppression, Portable Extinguishers, and Emergency / Exit Lights Inspection