8/5/22 confirmed via email with Audra K. for 8/8/22 in the afternoon. DH Sent email regarding inspection. DH Sprinkler Inspection Annual Fire Sprinkler Inspection (1 Wet System) Deficiency: No there is no evidence of five year hydro test on fire department connection Deficiency: There is no evidence of five-year internal obstruction investigation of sprinkler system Riser Deficiency: There is no evidence of five-year internal inspection of fire department connection check valve Deficiency: Sprinkler system days is outdated and should be replace Deficiency: There are sprinkler heads in quality lab that are missing two piece discussion the sprinkler heads were in place and the ceiling is sagging the ceiling wires will have to be drawn up in order for the ceiling to hang properly and then these escutcheons can be installed.