2710 Northridge Dr. Suite #F
Grand Rapids, MI 49544
1-800-968-2871

Our Top Cities


Job Locations
for grandville, mi


Map of Grandville MI
William S.

William S.


Job Checkin

Wet 1- In laundry room On riser: Pull (6) quick response sprinkler heads dated 1998 and send to UL for testing. These heads have been in service for more than 20 years and are due for testing. New sprinkler heads will be installed in place of the ones pulled. NFPA 25 (5.3.1.1.1.3) Sprinklers manufactured using fast-response elements that have been in service for 20 years shall be replaced, or representative samples shall be tested and then retested at 10-year intervals. Wet 2- In laundry room On riser: Replenish the missing spare sprinkler heads in the spare headbox. NFPA 25 (5.4.1.5.4) The stock of spare sprinklers shall include all types and ratings installed and shall be as follows; Facilities having 300-1000 sprinklers – minimum of 12 spare sprinklers Wet 2- In laundry room On riser: Install the missing escutcheon on the sprinkler head in the storage room next to the guest laundry on the 2nd floor. NFPA 25 (5.2.1.1.5) Escutcheons and cover plates for recessed, flush,