FACP BOILER MECHANICAL: Panel in alarm upon arrival and has power trouble as well. Checked the charging circuit and it is at 14.4 volts. Dropped power and panel died. Batteries are at 8.8/9.0 volts. Panel has a bad charging circuit and needs to be replaced. It is a Fire-Lite MS-4 panel. Both batteries need to be replaced as well. (2) 12V 7AH batteries. Zone 2 is the zone in alarm and trouble. Tried to resistor the zone, the trouble light goes off but the alarm remains. - repair This quote is for the replacement of the bad fire alarm panel. This quote includes. Panel Replacement, Installation & Testing. If permits are required an additional quote will be provided.