12/3 Scheduled with Brandon, emailed Derek with appt. FSM EXT tech will be on site too. km Kitchen Suppression Inspection Semi-Annual Kitchen Suppression System Inspection Ansul R102-D6 (2)360 links (8)Nozzles Ansul R102-T9 (1)500 link (4)360 links (18)Nozzles Deficiency: Number of Systems failed : 1 Inoperable Deficiency for Ansul R-102 9 Gallon Right Side of Hood: Exhaust fan on main kitchen(North) not working prior to test.