Terrence  J.

Terrence J.


Job Checkin

Deficiency: All repair work done within less work order will need a permit from the city of Southfield that says these corrections are being made due to alterations in building. Deficiency: We must move sprinkler heads and dry storage further back and add one in the middle per fire marshal to accommodate ordinary hazard classification instead of light hazard classification within storage room. Deficiency: There must be two 155° chrome pendant heads quick response in the hall on second floor by kitchen. Deficiency: There are approximately five mirage sprinkler head covers they need to be replaced in women’s locker room Deficiency: One warranty item that will be needed then relocate their sprinkler head and fitness center approximately two heads edit and two heads moved.