2/27/24 Confirmed with Niko for 2/28/24 in the afternoon. DH / Sent email regarding inspection DH Sprinkler Inspection Annual Sprinkler Inspection Deficiency: Sprinkler system number one is due for internal obstruction investigation of piping. 2- victaulic couplings Deficiency: Sprinkler system number one is due for internal inspection of check valve. Fire department connection. 2- victaulic couplings Deficiency: Sprinkler system number one is due for Hydro test fire department connection. 1- victaulic coupling Deficiency: Dry pendant, heads in cooler are due to be replaced. 4–286° chrome pendant adjustable, sprinkler heads quick response these are dry pendant heads Deficiency: Sprinkler system number two is due for five-year internal obstruction investigation of piping. 2- 4” victaulic couplings