2710 Northridge Dr. Suite #F
Grand Rapids, MI 49544
1-800-968-2871

Our Top Cities


Job Locations
for westland, mi


Map of Westland MI
Terrence  J.

Terrence J.


Job Checkin

9/28/22 Confirmed with Lindsey via cell for 10/4/22 at 8:00am DH Sprinkler Inspection Annual Fire Sprinkler Inspection (1 Wet System) Deficiency: No evidence of 5 year internal pipe obstruction investigation. Deficiency: There is no evidence of five-year FDC check valve inspection. Deficiency: There is no evidence of five-year FDC hydrostatic test. Deficiency: Missing stortz cap. Deficiency: Control valve tampers do not operate. Will need chain and lock. Deficiency: Gauges are outdated. Deficiency: Missing ITV sign. In back of pharmacy. Deficiency: Missing control valve sign. Deficiency: Suggested sprinkler adjustments need.