For this super tune-up I inspected the customers air handler and condenser, for the most part all equipment was measuring with the manufacturers specs with the exception of the compressor over amping on startup. The compressor was pulling 171 amps on startup with a maximum amp draw of 152 amps. With high amps the compressor is working harder than it should and it can cause the compressor to shut down or lockout. I recommend installing either a hard start kit or soft start kit the difference in the two is a hard start kit lowers amp draws by roughly 30% however a soft start kit will lower in Rush amps by 80 to 90%.