1412 Greenwood Road
Weatherford, TX 76008
817-596-4808

Our Top Cities


Job Locations
for azle, tx


Map of Azle TX
Kellen M.

Kellen M.


Job Checkin

Electrical - 5/19/25. 2 location noticed high voltage wires outside of proper junction. Plumber - 5/19/25. Concerns about toilet gurgling and possible vent stack cleaning. CA for condenser unit - 5/19/25 afternoon. An awning has been on the outdoor unit for a long time restricting proper heat rejection. Stressing components out which reduces efficiency and longevity. Expired manufacturer warranty. Homeowner will remove awning soon. Dual run capacitor is failing. Thermostat is incorrect and not allowing proper function. Condenser fan motor is not reaching RLA. The awning is a major issue do to the incorrect refrigerant readings by any well trained professional. All of my readings indicates improper charge of refrigerant. We discussed IAQ as there is ever so slight onset of biological growth present in the indoor unit on the evaporator coil head. 1" filter. No primary SAFTEY float switch. TESP tested within manufacturer tolerance. Homeowner to make a decision after CA appointment.