Tech Cody arrived to customer's home and met the homeowner. Main house system is a 6yo amana heat pump, pool house is a 11yo comfort maker heat pump. Main House: INDOOR: System had a temperature split of 19 degrees, I replaced the filter, the coil was clean, UV light was installed and operating normally, the blower was clean, the blower motor was in good condition, the heat strips were functioning within range. OUTDOOR: I washed and waxed the unit before taking any readings, the compressor and fan motor were operating within manufacturer range, the auxiliary motor starter was within tolerance, the unit had a compressor saver installed. The refrigerant charge was within acceptable levels at this time. Pool House: INDOOR: System had a temperature split of 18 degrees, the homeowner will get a replacement filter for the unit today, the coil was clean, the blower was clean, the blower motor was in good condition. OUTDOOR: I washed the unit before taking any readings. The compressor and