For this evaluation the customers condenser fan motor had seized up so the system was not cooling even with the compressor running. So to the customer about his options and that this time he wanted to just replace the condenser fan motor which I did and changed out the capacitor as well so it would match that motor. Tested everything out and the refrigerant levels in the system look good however the TXV appears to be restricted as I had a 10° sub cool and a 26° superheat with the system only producing an 11° Delta.