For this evaluation the customer system was not cooling, the indoor unit was running however the outdoor was throwing an L2 or high pressure cut off fault. But I reset the system pressures looked within range however decompressor was pulling 24 amps with a maximum rla of 20. There is a restriction inside the condenser filter drier causing the system to pull extremely high running amps. Per Ryan we are going to DOA the condenser and rush order a new one for the customers.