Replaced faulty air temperature sensor. Now reading temperature correctly. Water is still making its way into airhandler cabinet due to blower pulling the condensation of the coil. The main reason this happens is due to a failed sheen on the evaporator coil wich was just replaced so is highly unlikely, or high static pressure, with a zoned system this is very likely. Found that the bypass damper which is there to relieve static pressure when one of the zones is closed is failed. It will open when a zone is closed but when the zone is reopened it will stay open causing it to recycle conditioned air, causing lower air temps and causing the condenser to cycle off and on more than it should.