For this evaluation I showed up to the customer's home and nothing was running. The house internal temperature was 82° and set to 72°. Initially I thought it might be the thermostat because the thermostat was set to cooling but I was not getting a call for cooling between C and Y at the furnace so I bypass the thermostat my wire nutting it at the wall and the furnace came on but the condenser did not. When I went to the outdoor unit the system was throwing an l6 fault for an Open start circuit and when I measured the hard start kit it was good however the capacitor had failed on the hermetic side. I was out here last July and replaced the capacitor and it had not even been a year yet so I went ahead and warranted that capacitor and replaced it. Once I replace the capacitor and hooked everything back up the system kicked on into second stage cooling.