For this evaluation the customer stated the furnace blower would stay running even when the outdoor unit was not running. There was no fault codes when I checked cool cloud and there was no call for cool at the condenser. The thermostat was indicating that it was any signal for cooling but it was only blowing ambient air. This system is a 2 stage heating and cooling system. Only Y1 was wired up, so I used an extra brown wire and connected that to Y2 on the thermostat and furnace control board thermostat plug. Once the system started running in second stage cooling I went back to the thermostat and raise the temperature so the system would shut off and it did however when I lower the temperature the system would not come back on unless I reset the thermostat indicating the thermostat is bad. Once the customer's replace the thermostat I believe that will fix the issue with the blower continuing to run even when there's no longer a call.