For this evaluation the customers system was not working at all. When I started in the attic and connected to the furnace via cool cloud the condenser was throwing a 04 fault code or locked rotor code. Looking back at the history this has happened a number of times so I recommend it to the customer that we install a hard start kit which she went ahead and allowed me to do. The initial LRA was 130A with a Max pull of 122A. After installing the hard start kit it brought the startup amperage on the compressor down to 86A. Customer would like to have a plumber come out Tuesday 17 June for some faucets to be replaced.