2016 3.5t hp attic horizontal. Expired manufacturers warranty- verified. System pushing auxiliary heat. Leaks detected in evaporator coil. Blower wheel has heavy buildup. Blower capacitor below manufacturers tolerance. Return duct falling apart. Poor duct design with multiple 90° angles. Disconnect prongs show visual energy distress. Compressor inrush amperage exceeds manufacturers specifications. Condenser fan motor amps exceed manufacturers specifications. Condenser fan capacitor below manufacturers tolerance. Primary electrical control contractor has extreme scorching. Refrigerant levels are below manufacturers tolerance. After sitting with and sharing all pertinent video/photo evidences of the systems performance, wife called husband and I spoke to him the same. CA appointment set 2/13/25 @6pm. Customer service ran a pre-approval. Wife works for a hospital so please ensure membership benefits and discounts where applicable. No IAQ product. Duct redesign is appropriat