Job Checkin

2012 2.5t hp closet upflow. Manufacturers warranty expired. Primary pan full. Leaks detected in evaporator coil. Oil streaks present. Freezing. Inrush amperage on compressor exceeds manufacturers specifications. Refrigerant charge below manufacturers specifications. Hard start kit pressure plate blown. Capacitor below tolerance. Sat with homeowner and shared all video and photo evidences. Explained in detail the energy usage, performance and saftey of the system. Homeowner is aware of the need to replace system. CA appointment set for 5pm Saturday 4/26/25 Systems functional but diminishing in performance.