2021 5t trane hp attic horizontal. TESP discovered to be above the manufacturer specifications. Drain line clear. Filter needs replacement. Blower wheel clean. Slight biological growth on blower wire housing. Dual run capacitor within tolerance. Refrigerant charge is acceptable. Condenser unit washed from the inside out with chemical. Inrush amperage exceeds manufacturer specifications. All performance concerns were discussed with homeowners, the decision to obtain a soft start kit and a Kool kap with a membership was made. Micro aire soft start flex and a Kool Kap needed. Holding for parts.