When technician arrived the Air Conditioner compressor was cycling off due to high head pressure because the condensor fan was not running. Checked dual capacitor it tested at 0 for fan and 9 for compressor and should have tested at 35/5. I showed this to the homeowner so it can be replaced to further inspect the unit. Replaced capacitor, checked volts, amps, temperature splits, refrigerant pressures including superheat and subcool, checked filter it's OK, checked blower, also checked AC contactor it is pitting pretty badly should be replaced. Got approved to replace contactor so got it replaced and tested, unit is working good at this time.