Unable to contact homeowner 2015 Carrier Gas Furnace Checked and tightened all electrical connections Tenant recently changed filters Drain was clear and draining Blower motor and wheel were acceptable Evaporator coil was acceptable 2015 Carrier Straight Cool Checked and tightened all electrical connections Compressor cap was within manufacture range Fan cap was out of manufacture tolerance(weak) Both capacitors and hard start are loose and need to be mounted to the unit properly Primary electrical unit was acceptable Refrigerant levels were acceptable at this time Fan blades and motor were acceptable Condenser coils were acceptable Cleared debris from bottom of the unit Washed condenser coils from inside out Waxed top of the unit Recommended replacement of both caps as one is failing and replace with a dual run cap to free up space and the securing the cap and hard start to the unit properly so no damage occurs