Compressor has mechanicaly failed Hot gas discharge is only 40 degrees above ambient whereas it should be 100 degrees above ambient - system delta 11 Reccomendation of replacement of Condensor unit Reccomended comfort advisor Reccomended compressor estimate Dead bird found on top of damper inside if duct routing into return box of unit System left on cool at exit