For this super tune-up I expected the customers upstairs and downstairs furnaces and condensers. For the most part all equipment was measuring within manufactures specs and running well. I did fine that the ignition components for the upstairs furnace are oxidized and corroded which I would recommend replacing. Additionally the downstairs system was over amping on startup and the dual run capacitor was slightly out of tolerance which I recommended replacing. The customer wanted to just have a hard start kit installed today and may have other recommendations installed or completed at a later date. The hard start kit reduced the startup amperage to the compressor to 85A from 140A.