For this job I performed a evaluation. Homeowners stated that earlier in the day when she called she heard a loud noise coming from the outdoor unit and then it shut off. Homeowner turned off the unit for a hour or so and then turned it back on and after that it has been cooling within normal limits. I ran through refrigerant and electrical components the only abnormality noted was that the compressor was over amping at startup. I suggested installing either a soft start kit or a compressor saver to avoid future compressor lockouts. No other significant abnormalities were noted during the evaluation. Homeowner opted to have estimates sent, they did not want to install either one of the recommended components at the moment but are considering to have it done in the future. Thank you for choosing comfort experts, have a great day!