2022 3t condenser. 2018 evaporator coil. 2006 gas furnace. NO MANUFACTURER WARRANTY. Indoor tramsitio from furnace to evaporator coil is questionable. Drain line clear. 1" filter in a 4" box - this filter gets blocked fast and must be replaced often. A blocked filter heavily restricts airflow which creates a vacuum inside the air handler. Blower - motor has visual breach of oil, wheel has buildup and the 7.5mfd capacitor is failing. TESP (total External Static Pressure) of 0.5 on the manufacturer data shows to be exceeding the pressure design. This test reveals dirty coil, failing blower motor and a filter that restricts too much airflow. Evaporator coil has buildup blockage which further restricts airflow. Compressor inrush amperage is exceeding the manufacturer specifications revealing an over working compressor. Condenser fan motor is not reaching proper FLA which indicates performance issues. 45/5mfd dual run capacitor is failing on the fan side. Refrigerant charge is hovering ju