1412 Greenwood Road
Weatherford, TX 76008
817-596-4808

Our Top Cities


Job Locations
for runaway bay, tx


Map of Runaway Bay TX
Mark D.

Mark D.


Job Checkin

Rudd air handler installed in 2004 with Lennox heat pump installed in 2019. Customer says that he keeps the thermostat on 82 in the summer time and the system can maintain. Tech discovered that the unit had high superheat with sub cooling in normal range. Found that the polarity was switched on the condenser fan motor and it was going the wrong way. Switched the polarity to the correct way and the superheat went into the normal range. The system shuts down on high pressure in heat pump mode. Believe there to be a possible blockage causing high pressures. The evap coil is original r-22 coil with r-410 heat pump installed outside. Talked to customer about options. Customer refused repairs.